FM series resonance voltage withstand test equipment product introduction:

Principle of frequency modulation series resonance withstand voltage test set in GIS test: GIS is a combination of circuit breakers, isolating switches, voltage transformers, current transformers, arresters, etc., and is insulated by SF6 gas. GIS is generally 2 -18 intervals, each interval in the test is equivalent to a capacitor. The voltage withstand test of GIS is equivalent to the withstand voltage test of this capacitor.
Product nickname:
Frequency modulation series resonance device, series resonance device, series resonance withstand voltage device, variable frequency series resonance complete device, frequency conversion resonance test device
Features:
1, small size, light weight, easy to operate
2, the blue screen displays test data, test status, and has real-time operation step prompt function
3, can flexibly set the test voltage, frequency modulation range, pressurization time, protection current
4, the test results can calculate the capacitance of the test
5, with computer communication interface, can communicate with the computer and test data management
6, there is real-time time display, can store 200 sets of test data
7, high resolution: frequency resolution is 0.01Hz
8, high security and reliability. The device has over current, over voltage, IPM and discharge protection functions, which can effectively protect people and equipment.
9, the test results can be printed
Technical Parameters:
1. Output test voltage: 0~500kV (multi-position) AC RMS
2. Output test current: 0.5~20A (multi-position) AC RMS
3. Output frequency: 30~200HZ (can be arbitrarily selected)
4, resonant voltage waveform: sine wave, waveform distortion rate <1%
5, the scope of the test: generators, power cables, transformers, capacitive voltage transformers, line insulation equipment.
6, working system: full power output, continuous working time 30 minutes
7, quality factor: 20~80
8, input working power: 220V (380V), 50HZ.
9, ambient temperature and relative humidity: 0 ° C ~ +40 ° C; <95%, no condensation

Transformer external test principle and precautions for FM series resonant withstand voltage test equipment:
The external test is a basic test to test the main insulation of the transformer. The test frequency is not less than 80% of the rated frequency.