18/30kV CU/XLPE/STA/PVC(or PE) Power Cable
1. Description
Construction: Compacted stranded circular copper conductor, extruded semi-conducting compound as conductor shield, cross-linked polyethylene (XLPE) insulation, semi-conducting compound as insulation shield, copper tape or combination of copper wire and tape as metallic screen, three cores assembled together with non-hygroscopic polypropylene filler, wrapped with binder tape, PVC inner covering as armoring bedding, double galvanized steel tape armored, PVC or PE outer sheath.
2. Operating Characteristics
Rated voltage U0/U(Um): 18/30(36)kV
U0 is the rated power frequency voltage between conductor and earth or metallic screen for which the cable is designed;
U is the rated power frequency voltage between conductors for which the cable is designed;
Um is the maximum value of the "highest system voltage" for which the equipment may be used.
Max. Permissible continuous operating temperature of conductor: 90 ° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed: 250 ° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 20 times of the diameter of cable
For three core cable: Not less than 15 times of the diameter of cable
3. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, outdoors, in tunnel or in cable trench, unable to bear external mechanical force.
Single core cable in magnetic duct is not permissible.
4. Manufacturing Standards
IEC 60502-2 and Chinese National Standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.
KINDLY NOTE: If you want to know more details about this kind of products, please visit our website:www.jytopcable.com  for further information.  Thanks.
Main technical data of 18/30KV, Single core, Copper conductor, XLPE insulated, double galvanized steel tape armored and PVC or PE sheath cable
CABLE CONSTRUCTION: 18/30KV CU/XLPE/DSTA/PVC or PE
  Size |
Nominal thickness of XLPE insulation(mm) | Approx. thickness of copper tape screen (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC or PE(mm) | Approx. overall diameter of finished cable(mm) | Max. conductor D.C resistance @ 20 0 C (Ω/km) |
1x50mm 2 | 8.0 | 0.12 | 0.5 | 2.1 | 37.0 | 0.387 |
1x70mm 2 | 8.0 | 0.12 | 0.5 | 2.1 | 38.7 | 0.268 |
1x95mm 2 | 8.0 | 0.12 | 0.5 | 2.2 | 40.5 | 0.193 |
1x120mm 2 | 8.0 | 0.12 | 0.5 | 2.3 | 42.1 | 0.153 |
1x150mm 2 | 8.0 | 0.12 | 0.5 | 2.3 | 43.9 | 0.124 |
1x185mm 2 | 8.0 | 0.12 | 0.5 | 2.4 | 45.7 | 0.0991 |
1x240mm 2 | 8.0 | 0.12 | 0.5 | 2.4 | 48.1 | 0.0754 |
1x300mm 2 | 8.0 | 0.12 | 0.5 | 2.5 | 50.5 | 0.0601 |
1x400mm 2 | 8.0 | 0.12 | 0.5 | 2.6 | 53.9 | 0.0470 |
1x500mm 2 | 8.0 | 0.12 | 0.5 | 2.7 | 58.0 | 0.0366 |
1x630mm 2 | 8.0 | 0.12 | 0.5 | 2.8 | 61.8 | 0.0283 |
1x800mm 2 | 8.0 | 0.12 | 0.5 | 3.0 | 66.2 | 0.0221 |
MIDDLE VOLTAGE 18/30 (33) KV Copper Conductor XLPE Insulated Steel Tape Armored Cable

18/30kV CU/XLPE/STA/PVC(or PE) Power Cable
1. Description
Construction: Compacted stranded circular copper conductor, extruded semi-conducting compound as conductor shield, cross-linked polyethylene (XLPE) insulation, semi-conducting compound as insulation shield, copper tape or combination of copper wire and tape as metallic screen, three cores assembled together with non-hygroscopic polypropylene filler, wrapped with binder tape, PVC inner covering as armoring bedding, double galvanized steel tape armored, PVC or PE outer sheath.
2. Operating Characteristics
Rated voltage U0/U(Um): 18/30(36)kV
U0 is the rated power frequency voltage between conductor and earth or metallic screen for which the cable is designed;
U is the rated power frequency voltage between conductors for which the cable is designed;
Um is the maximum value of the "highest system voltage" for which the equipment may be used.
Max. Permissible continuous operating temperature of conductor: 90 ° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed: 250 ° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 20 times of the diameter of cable
For three core cable: Not less than 15 times of the diameter of cable
3. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, outdoors, in tunnel or in cable trench, unable to bear external mechanical force.
Single core cable in magnetic duct is not permissible.
4. Manufacturing Standards
IEC 60502-2 and Chinese National Standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.
KINDLY NOTE: If you want to know more details about this kind of products, please visit our website:www.jytopcable.com  for further information.  Thanks.
Main technical data of 18/30KV, Single core, Copper conductor, XLPE insulated, double galvanized steel tape armored and PVC or PE sheath cable
CABLE CONSTRUCTION: 18/30KV CU/XLPE/DSTA/PVC or PE
  Size |
Nominal thickness of XLPE insulation(mm) | Approx. thickness of copper tape screen (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC or PE(mm) | Approx. overall diameter of finished cable(mm) | Max. conductor D.C resistance @ 20 0 C (Ω/km) |
1x50mm 2 | 8.0 | 0.12 | 0.5 | 2.1 | 37.0 | 0.387 |
1x70mm 2 | 8.0 | 0.12 | 0.5 | 2.1 | 38.7 | 0.268 |
1x95mm 2 | 8.0 | 0.12 | 0.5 | 2.2 | 40.5 | 0.193 |
1x120mm 2 | 8.0 | 0.12 | 0.5 | 2.3 | 42.1 | 0.153 |
1x150mm 2 | 8.0 | 0.12 | 0.5 | 2.3 | 43.9 | 0.124 |
1x185mm 2 | 8.0 | 0.12 | 0.5 | 2.4 | 45.7 | 0.0991 |
1x240mm 2 | 8.0 | 0.12 | 0.5 | 2.4 | 48.1 | 0.0754 |
1x300mm 2 | 8.0 | 0.12 | 0.5 | 2.5 | 50.5 | 0.0601 |
1x400mm 2 | 8.0 | 0.12 | 0.5 | 2.6 | 53.9 | 0.0470 |
1x500mm 2 | 8.0 | 0.12 | 0.5 | 2.7 | 58.0 | 0.0366 |
1x630mm 2 | 8.0 | 0.12 | 0.5 | 2.8 | 61.8 | 0.0283 |
1x800mm 2 | 8.0 | 0.12 | 0.5 | 3.0 | 66.2 | 0.0221 |
Micro switches
Micro switches, as the name suggests, use very small force switches. It is the switch that the external mechanical force acts on the moving reed through the transmission element, and the fixed contact and the moving contact at the end of the driving reed are quickly turned on or off. There are small, ultra-small, super-small and so on in size. Functionally waterproof. Furthermore, Metal Switches, Automotive Switches, Push Button Switches are also our competitive products.
This Mini Micro Switches are used for automatic control and safety protection in devices that need frequent switching circuits. They are widely used in electronic equipment, instrumentation, mining, power systems, household appliances, electrical equipment, and aerospace, aviation, ships, missiles, and so on. Tanks and other military fields have been widely used in the above fields. The switch is small, but it plays an irreplaceable role.
There are many kinds of Waterproof Micro Switches, and there are hundreds of internal structures. There are common type, small size and super small size according to the volume. According to the protective performance points, there are waterproof type, dust-proof type, and explosion proof type; according to the dividing form, there are Single type, double type, multiple type.
The Electric Micro Switches, has a small contact spacing and a quick acting mechanism, and the contact mechanism that performs the switching action with a prescribed stroke and force is covered by the outer casing, and has an external actuator and a small outer shape.
Micro Switches,Waterproof Micro Switches,Mini Micro Switch,Metal Micro Switch
YESWITCH ELECTRONICS CO., LTD. , https://www.yeswitches.com